NEC GFCI Requirements
NEC 2023 · Article 210.8 · Quick Reference
!
Estimating impact: Missed GFCI requirements are the #1 code catch in Vernier plan reviews. Every unforeseen GFCI receptacle is a change order. Price them in your bid — they're never cheaper in the field.
Required Locations — Dwelling Units (210.8(A))
LocationSpecific TriggerNotes / Exceptions
BathroomsAll receptaclesRegardless of distance from sink or tub
GaragesAll receptaclesIncluding accessory buildings with floors at or below grade
OutdoorsAll receptaclesIncludes balconies, decks, porches with direct access from dwelling
Crawl spacesAll receptacles at or below gradeGrade level and below only
Unfinished basementsAll receptaclesException: single dedicated receptacle for a permanently installed appliance
KitchensAll countertop receptaclesWithin 6 ft of any sink — entire countertop surface
Laundry, utility, wet bar sinksWithin 6 ft of edge of sinkMeasured along countertop surface
BoathousesAll receptacles
Required Locations — Commercial / Industrial (210.8(B))
LocationSpecific TriggerDistance Rule
BathroomsAll receptaclesNo distance qualification
KitchensReceptacles serving countertop surfacesAll countertop circuits
RooftopsAll 125V to 250V, 15A-60A receptacles
OutdoorsAll receptaclesIncludes covered but exposed locations
Garages, service baysAll 125V–250V, 15A–60A, single-phase receptaclesExcludes dedicated equipment receptacles not readily accessible
Indoor service areasAll receptacles within 6 ft of sinks, tubs, or shower stallsMeasured along countertop surface
Locker rooms with showersAll receptacles
Crawl spacesAll receptacles at or below grade
Unfinished portions of basementsAll receptacles
GFCI Methods Accepted
MethodProtects
GFCI receptacleThat receptacle only (unless wired to protect downstream)
GFCI breakerEntire branch circuit
GFCI receptacle (downstream)All outlets fed from its LOAD terminals
GFCI portable deviceOnly where temp power permits it per 590.6
Key Exceptions — Commercial
ExceptionCondition
Exempt — dedicated receptacleSingle receptacle for permanently installed appliance, not readily accessible
Exempt — industrial machinery210.8(B) Ex. — industrial process equipment receptacles not readily accessible
Periodic testing requiredTest button per UL 943; replace if trip doesn't occur
i
Medical locations (Article 517): Patient care areas have different requirements — standard GFCI may not be acceptable. In patient care areas, isolated power systems or specific hospital-grade GFCI types are required per 517.20. Flag all medical projects for separate review.